Output | |
---|---|
DC Voltage | 12V |
Rated current | 10A |
Current Range | 0÷10A |
Rated Power | 120W |
Ripple & noise (max.) | 120mVp-p |
Voltage adjustment range | 12÷15V |
Voltage tolerance | ±1.5% |
Line regulation | ±0.5% |
Load regulation | ±0.5% |
Setup & rise time |
2000ms & 70ms/400VAC at full load, 2000ms & 70ms/230VAC at full load |
Hold up time (typ.) |
50ms/400VAC at full load, 50ms/230VAC at full load |
Input | |
Voltage range |
180÷550VAC, 254÷780VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 89,5% |
AC current (typ.) |
0.55A/115VAC, 1.2A/230VAC |
Inrush current (typ.) | 50A |
Leakage current | <3,5mA/530VAC |
Protection | |
Overload |
105%÷130% rated output power, protection type - constant current limiting - recovers automatically after fault condition is removed |
Overvoltage |
16÷18V, protection type - shut down o/p voltage & re-power on to recover |
Over temperature |
105°C ±5°C (TSW1) detect on heatsink of power transistor, protection type - shut down o/p voltage & re-power on to recover |
Environment | |
Working temperature | -25°C ÷ 70°C |
Working humidity | 20÷95% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, UL60950-1, TUV EN60950-1 |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC, I/P-FG 100MΩ/500VDC, O/P-FG 100MΩ/500VDC |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level criteria A |
Others | |
MTBF | min. 268000h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 40mm x 125,2mm x 113,5mm |
Weight | 0,65kg |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 10A |
Current Range | 0÷10A |
Rated Power | 240W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 24÷28V |
Voltage tolerance | ±1.0% |
Line regulation | ±0.5% |
Load regulation | ±1.0% |
Setup & rise time |
800ms & 150ms/400VAC at full load, 1500ms & 150ms/230VAC at full load |
Hold up time (typ.) |
18ms/400VAC at full load, 18ms/230VAC at full load |
Input | |
Voltage range |
180÷550VAC, 254÷780VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 91% |
AC current (typ.) |
1A/400VAC, 2A/230VAC |
Inrush current (typ.) | 50A |
Leakage current | <3,5mA/530VAC |
Protection | |
Overload |
105%÷130% rated output power, protection type - constant current limiting - recovers automatically after fault condition is removed |
Overvoltage |
29÷33V, protection type - shut down o/p voltage & re-power on to recover |
Over temperature |
90°C ±5°C (TSW1) detect on heatsink of power transistor, protection type - shut down o/p voltage & re-power on to recover |
Environment | |
Working temperature | -30°C ÷ 70°C |
Working humidity | 20÷95% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, UL60950-1, TUV EN60950-1 |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC, I/P-FG 100MΩ/500VDC, O/P-FG 100MΩ/500VDC |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level criteria A |
Others | |
MTBF | min. 268000h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 63mm x 125,2mm x 113,5mm |
Weight | 1,06kg |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 20A |
Current Range | 0÷20A |
Rated Power | 480W |
Ripple & noise (max.) | 100mVp-p |
Voltage adjustment range | 24÷28V |
Voltage tolerance | ±1.0% |
Line regulation | ±0.5% |
Load regulation | ±1.0% |
Setup & rise time |
800ms & 150ms/400VAC at full load, 2000ms & 150ms/230VAC at full load |
Hold up time (typ.) |
18ms/400VAC at full load, 16ms/230VAC at full load |
Input | |
Voltage range |
180÷550VAC, 254÷780VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 92% |
AC current (typ.) |
1.6A/400VAC, 4A/230VAC |
Inrush current (typ.) | 50A |
Leakage current | <3,5mA/530VAC |
Protection | |
Overload |
105%÷130% rated output power, protection type - constant current limiting - recovers automatically after fault condition is removed |
Overvoltage |
29÷33V, protection type - shut down o/p voltage & re-power on to recover |
Over temperature |
95°C ±5°C (TSW1) detect on heatsink of power transistor, protection type - shut down o/p voltage & re-power on to recover |
Environment | |
Working temperature | -30°C ÷ 70°C |
Working humidity | 20÷95% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, UL60950-1, TUV EN60950-1 |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC, I/P-FG 100MΩ/500VDC, O/P-FG 100MΩ/500VDC |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level criteria A |
Others | |
MTBF | min. 268000h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 85.5mm x 125.2mm x 128.5mm |
Weight | 1.7kg |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 0.42A |
Current Range | 0÷0.42A |
Rated Power | 10W |
Ripple & noise (max.) | 150mVp-p |
Voltage tolerance | ±2.0% |
Line regulation | ±1.0% |
Load regulation | ±2.0% |
Setup & rise time |
500ms & 30ms/230VAC at full load, 1000ms & 30ms/115VAC at full load |
Hold up time (typ.) |
120ms/230VAC at full load, 25ms/115VAC at full load |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 84% |
AC current (typ.) |
0.33A/115VAC, 0.21A/230VAC |
Inrush current (typ.) |
35A/115VAC cold start, 70A/230VAC cold start |
Leakage current | <1mA/240VAC |
Protection | |
Overload |
above 105% rated output power, protection type - Hiccup mode - recovers automatically after fault condition is removed |
Overvoltage |
27.6÷32.4V, protection type - shut down o/p voltage & re-power on to recover |
Function | |
DC OK active signal | 18÷27V/20mA |
Environment | |
Working temperature | -20°C ÷ 70°C |
Working humidity | 20÷90% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, TUV EN60950-1, NEC class 2 / LPS |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC, I/P-FG 100MΩ/500VDC, O/P-FG 100MΩ/500VDC |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-1, EN61204-3, light industry level criteria A |
Others | |
MTBF | min. 584000h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 22.5mm x 90mm x 100mm |
Weight | 0.17kg |
Warranty | 3 years |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 1A |
Current Range | 0÷1A |
Rated Power | 24W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 21.6÷26.4V |
Voltage tolerance | ±1.0% |
Line regulation | ±1.0% |
Load regulation | ±1.0% |
Setup & rise time |
500ms & 30ms/230VAC at full load, 1000ms & 30ms/115VAC at full load |
Hold up time (typ.) |
50ms/230VAC at full load, 20ms/115VAC at full load |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 84% |
AC current (typ.) |
0.55A/115VAC, 0.35A/230VAC |
Inrush current (typ.) |
20A/115VAC cold start, 40A/230VAC cold start |
Leakage current | <1mA/240VAC |
Protection | |
Overload |
105%÷160% rated output power, protection type - constant current limiting - recovers automatically after fault condition is removed |
Overvoltage |
27.6÷32.4V, protection type - shut down o/p voltage & re-power on to recover |
Function | |
DC OK active signal | 18÷27V/20mA |
Environment | |
Working temperature | -20°C ÷ 70°C |
Working humidity | 20÷90% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, TUV EN60950-1, NEC class 2 / LPS |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC, I/P-FG 100MΩ/500VDC, O/P-FG 100MΩ/500VDC |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-1, EN61204-3, light industry level criteria A |
Others | |
MTBF | min. 236900h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 22.5mm x 90mm x 100mm |
Weight | 0.19kg |
Warranty | 3 years |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 1.7A |
Current Range | 0÷1.7A |
Rated Power | 40.8W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 24÷30V |
Voltage tolerance | ±1.0% |
Line regulation | ±1.0% |
Load regulation | ±1.0% |
Setup & rise time |
500ms & 30ms/230VAC at full load, 500ms & 30ms/115VAC at full load |
Hold up time (typ.) |
50ms/230VAC at full load, 20ms/115VAC at full load |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 88% |
AC current (typ.) |
1.1A/115VAC, 0.7A/230VAC |
Inrush current (typ.) |
30A/115VAC cold start, 60A/230VAC cold start |
Leakage current | <1mA/240VAC |
Protection | |
Overload |
105%÷150% rated output power, protection type - constant current limiting - recovers automatically after fault condition is removed |
Overvoltage |
31.2÷36V, protection type - shut down o/p voltage & re-power on to recover |
Function | |
DC OK signal relay contact rating (max.) | 30V/1A resistive |
Environment | |
Working temperature | -20°C ÷ 70°C |
Working humidity | 20÷90% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, UL60950-1, TUV EN60950-1, NEC class 2 / LPS |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC 25°C 70%RH, I/P-FG 100MΩ/500VDC 25°C 70%RH, O/P-FG 100MΩ/500VDC 25°C 70%RH |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level criteria A |
Others | |
MTBF | min. 301700h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 40mm x 90mm x 100mm |
Weight | 0.3kg |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 2.5A |
Current Range | 0÷2.5A |
Rated Power | 60W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 24÷30V |
Voltage tolerance | ±1.0% |
Line regulation | ±1.0% |
Load regulation | ±1.0% |
Setup & rise time |
500ms & 30ms/230VAC at full load, 500ms & 30ms/115VAC at full load |
Hold up time (typ.) |
50ms/230VAC at full load, 20ms/115VAC at full load |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Frequency range | 47÷63Hz |
Efficiency (typ.) | 88% |
AC current (typ.) |
1.8A/115VAC, 1A/230VAC |
Inrush current (typ.) |
30A/115VAC cold start, 60A/230VAC cold start |
Leakage current | <1mA/240VAC |
Protection | |
Overload |
105%÷150% rated output power, protection type - constant current limiting - recovers automatically after fault condition is removed |
Overvoltage |
31.2÷36V, protection type - shut down o/p voltage & re-power on to recover |
Function | |
DC OK signal relay contact rating (max.) | 30V/1A resistive |
Environment | |
Working temperature | -20°C ÷ 70°C |
Working humidity | 20÷90% RH non-condensing |
Storage temperature | -40°C ÷ 85°C |
Storage Humidity | 10÷95% RH |
Temperature coefficient | ±0.03%/°C (0÷50°C) |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Vibration (mounting) | compliance to IEC60068-2-6 |
Safety & EMC | |
Safety standards |
UL508, UL60950-1, TUV EN60950-1, NEC class 2 / LPS |
Withstand voltage |
I/P-O/P 3kVAC, I/P-FG 1.5kVAC, O/P-FG 0.5kVAC |
Isolation resistance |
I/P-O/P 100MΩ/500VDC 25°C 70%RH, I/P-FG 100MΩ/500VDC 25°C 70%RH, O/P-FG 100MΩ/500VDC 25°C 70%RH |
EMI conduction & radiation |
EN55011, EN55022 (CISPR22), EN61204-3 Class B |
Harmonic current |
EN61000-3-2, EN61000-3-3 |
EMS immunity |
EN61000-4-2/3/4/5/6/8/11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level criteria A |
Others | |
MTBF | min. 299200h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 40mm x 90mm x 100mm |
Weight | 0.33kg |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 0.63A |
Rated Power | 15W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 21.6÷29.0V |
Voltage tolerance | ±1.0% |
Line regulation | ±1.0% |
Load regulation | ±1.0% |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Efficiency (typ.) | 86% |
Protection | |
Overload |
105%÷160% rated output power, protection type - constant current limiting - recovers automatically |
Overvoltage |
115%÷150%, protection type - shut down , clamp by zener diode |
Environment | |
Working temperature | -30°C ÷ 70°C |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Safety & EMC | |
Safety standards |
UL62368-1, UL508, TUV EN61558-2-16, IEC62368-1, EAC Tp TC 040, BSMI CNS14336-1 approved |
Withstand voltage | I/P-O/P 4kVAC |
EMC Standards |
EN55032 class B, EN61000-3-2,33, EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, EN61204-3 |
Others | |
MTBF | min. 441500h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 17.5mm x 90mm x 5.5mm |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 1.5A |
Current Range | 0÷1.5A |
Rated Power | 30W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 21.6÷29.0V |
Voltage tolerance | ±1.0% |
Line regulation | ±1.0% |
Load regulation | ±1.0% |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Efficiency (typ.) | 89% |
Protection | |
Overload |
105%÷160% rated output power, protection type - constant current limiting - recovers automatically |
Overvoltage |
115%÷150%, protection type - shut down & re-power on to recover |
Environment | |
Working temperature | -30°C ÷ 70°C |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Safety & EMC | |
Safety standards |
UL62368-1, UL508, TUV EN61558-2-16, IEC62368-1, EAC Tp TC 040, BSMI CNS14336-1 approved |
Withstand voltage | I/P-O/P 4kVAC |
EMC Standards |
EN55032 class B, EN61000-3-2,33, EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, EN61204-3 |
Others | |
MTBF | min. 441500h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 35mm x 90mm x 5.5mm |
Output | |
---|---|
DC Voltage | 24V |
Rated current | 2.5A |
Current Range | 0÷2.5A |
Rated Power | 60W |
Ripple & noise (max.) | 150mVp-p |
Voltage adjustment range | 21.6÷29.0V |
Voltage tolerance | ±1.0% |
Line regulation | ±1.0% |
Load regulation | ±1.0% |
Input | |
Voltage range |
85÷264VAC, 120÷370VDC |
Efficiency (typ.) | 60% |
Protection | |
Overload |
105%÷160% rated output power, protection type - constant current limiting - recovers automatically |
Overvoltage |
115%÷150%, protection type - shut down & re-power on to recover |
Environment | |
Working temperature | -30°C ÷ 70°C |
Vibration (component) |
10÷500Hz, 2G 10min./1cycle, 60min. each along X Y Z axes |
Safety & EMC | |
Safety standards |
UL62368-1, UL508, TUV EN61558-2-16, IEC62368-1, EAC Tp TC 040, BSMI CNS14336-1 approved |
Withstand voltage | I/P-O/P 4kVAC |
EMC Standards |
EN55032 class B, EN61000-3-2,33, EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, EN61204-3 |
Others | |
MTBF | min. 441500h MIL-HDBK-217F (25°C) |
Dimension (W x H x D) | 52.5mm x 90mm x 5.5mm |
Page 1 of 2
|